Capacitive Level Sensor – Continuous 4–20 mA, up to 200 °C

A capacitive level sensor uses a probe inside the tank: as the liquid level changes, the capacitance between probe and tank wall changes and is converted to 4–20 mA or 0–10 V. No moving parts, probe rated up to 200 °C, 1 % accuracy, IP67 – ideal for boiler water level, tanks and vessels. ISE supplies it in line with European EN 61326-1 and EN 60529.

Capacitive level sensor

How a capacitive level sensor works

Capacitive level and optical level switch principles
Capacitive level and optical level switch principles

Probe and tank wall (or reference tube) form a capacitor. Liquids have a higher dielectric constant than air (water εr ≈ 80), so capacitance rises linearly with level. Set 0 % and 100 % on the actual liquid.

Capacitive level sensor specifications

SPECIFICATIONS
Supply:
– Current output (var. „I“) 9 … 34  V DC
– Voltage output (var. „U“) 12  … 34  V DC
Output type (var. “I”) 4 … 20 mA (2-wire)
Output type (var. “U”) 0 … 10  V (3-wire)
Accuracy 1%
Ambient temperature -40 … +85°C
Probe operating rating -40 … +200°C
Thread Thread M27x2 ; M30x1,5
G ¾“ – NPT¾ TriClamp
Ingress protection IP67

Capacitive level installation 1

Choosing the right level technology

Choosing a level technology: radar, ultrasonic, capacitive, optical, paddle, DP
Choosing a level technology: radar, ultrasonic, capacitive, optical, paddle, DP

Applications

  • Boiler water level, condensers, hot water tanks – see the capacitive boiler level probe.
  • Oil, fuel and chemical tanks, small vessels.
  • Hygienic CIP tanks (TriClamp).

Reference standards

Standard Scope
EN 61326-1 EMC
EN 60529 IP67
EN 12953-9 Boiler water level limiting devices (for boiler use)