Boiler Fan Control with VFDs for Boilers and Thermal Oil Heaters – EU Standard

Boiler fan control with variable speed drives (VFDs) is the most effective way to cut the power drawn by forced-draft (FD), induced-draft (ID) and fluidising fans while keeping furnace pressure stable and combustion efficient. ISE designs, supplies and programs fan control systems for steam boilers and thermal oil heaters following European practice (EN 12953-7, EN 12952-8, Regulation (EU) 2019/1781).

Boiler fan control system with VFDs: FD fan, ID fan, furnace pressure and O₂
Boiler fan control system with VFDs: FD fan, ID fan, furnace pressure and O₂

Why boiler fan control matters

Fans are the largest electrical load on a boiler. Boilers rarely run at full load, so airflow must follow steam pressure or thermal oil temperature. If fans run at full speed and air is throttled by dampers, the surplus energy is lost as pressure drop, motors and bearings run fully loaded, furnace pressure fluctuates and high excess air lowers combustion efficiency.

Boiler types and fan configuration

Boiler fan control configuration by boiler type: burner, fixed grate, chain grate, fluidised bed
Boiler fan control configuration by boiler type: burner, fixed grate, chain grate, fluidised bed
Boiler type Fans Main control point
Oil (DO, HFO) or gas (LPG, CNG, biogas) burner boilers Burner combustion-air fan VFD + O₂ trim; burners to EN 267 / EN 676
Fixed-grate boilers Under-grate FD fan, ID fan FD on load, ID on furnace pressure
Chain-grate stokers Zoned primary air, overfire air, ID fan Plus grate speed VFD on load
Fluidised-bed boilers High-pressure fluidising fan, secondary air, ID fan Hold minimum fluidising airflow
Thermal oil heaters As above Load on oil outlet temperature; prove oil flow before firing

Boiler fan control: damper versus VFD

Boiler fan power: damper control versus variable speed drive
Boiler fan power: damper control versus variable speed drive

Damper control

The fan always runs at full speed; airflow and head are adjusted by opening or closing dampers.

  • Pros: low initial cost.
  • Cons: high energy loss, high inrush current, faster wear of motors, bearings and dampers; dampers stick and control is slow and imprecise.

Variable speed drive control

The fan runs at the speed the load needs, set by a 4–20 mA or fieldbus signal from the PLC. By the fan affinity laws, flow follows speed, pressure follows speed squared and power follows speed cubed – 80 % speed needs only about 51 % power.

  • Pros: typically 30–50 % energy saving on variable loads; soft start; longer motor and equipment life; faster, more accurate control; less maintenance.
  • Cons: higher investment; harmonics and EMC must be handled correctly.

Field example: at the Valorsul waste-to-energy plant in Portugal, replacing damper control with drives on three ID fans and three secondary air fans cut consumption by about 9 MWh/day, saving about €240,000 a year with a payback of about 3 years (ABB case note). For small and medium industrial boilers, payback is typically 1–3 years depending on fan power and running hours.

Fan and combustion control loops

Boiler fan control loops: load PID, O₂ trim, furnace pressure, feed-forward
Boiler fan control loops: load PID, O₂ trim, furnace pressure, feed-forward
  1. Load loop (master): compares steam pressure or oil outlet temperature with setpoint and drives the fuel-feed and FD fan VFDs in air/fuel ratio with cross-limiting (on load increase air leads; on decrease fuel leads).
  2. O₂ trim: an oxygen analyzer in the flue gas fine-tunes excess air – see boiler oxygen trim control.
  3. Furnace pressure loop: a differential pressure sensor (±250 Pa) measures furnace pressure and a PID drives the ID fan VFD to hold −20 … −50 Pa, with feed-forward from the FD fan.
  4. Safety interlocks: pre-purge, minimum fan speed, trip on loss of air or high furnace pressure – independent of the control PLC per EN 50156-1 and EN 12953-7.

EU standards for boiler fan control

Standard Scope
EN 12953-7 / EN 12952-8 Firing system requirements for shell / water-tube boilers, air–fuel interlocks
EN 676 / EN 267 Forced-draught burners for gaseous / liquid fuels, air ratio control
EN 50156-1 Electrical equipment of furnaces, safety systems
Regulation (EU) 2019/1781 Drives minimum IE2; motors IE3 (0.75–1000 kW), IE4 (75–200 kW) from July 2023
Regulation (EU) 327/2011 Minimum efficiency of fans 125 W – 500 kW
EN 61800-3 / EN 61000-3-12 Drive EMC and harmonics
DIN 4754-1 Safety of thermal oil installations

Benefits of ISE boiler fan control

  • 30–50 % lower fan energy on variable loads.
  • Stable furnace pressure, no puff-back; optimum combustion with O₂ trim and lower fuel use.
  • Soft start, fewer mechanical failures, lower maintenance.
  • Operating data to SCADA, supporting continuous emission monitoring and energy reporting.

Project steps

  1. Survey fans, motors, load profile and running hours; estimate savings.
  2. Select IE2 drives, line reactors/harmonic filters and IE3/IE4 motors where replacement is needed.
  3. Install differential pressure, O₂ and load (pressure/temperature) sensors.
  4. Program the PLC: load loop, O₂ trim, furnace pressure, safety interlocks; HMI/SCADA integration.
  5. Commissioning, tuning and operator training.

FAQ

Should the dampers be kept after installing VFDs?

Yes, kept fully open for bypass operation or cold start; flow control moves to the drives.

Does the ID fan need a VFD if the FD fan has one?

Yes. If FD airflow drops while the ID fan runs at full speed, the furnace becomes too negative, increasing air ingress and heat loss. Controlling both keeps furnace pressure stable.

Related

Contact ISE about boiler fan control

EQUIPMENT INDUSTRIAL SOLUTION CO., LTD (ISE) – Ho Chi Minh City, Vietnam.

Contact us: Sales +84 909 617 185 – Technical +84 979 117 185 – Email: [email protected]

Scroll to Top